Storage Pressure: | 1.6MPa |
---|---|
Max Working Pressure: | 2.5MPa |
Fire Extinguishing Method: | Fully Flood Extinguishing |
Color: | Red |
Starting Mode: | Automatic, Electrical Manual, Mechanical Emergency |
Power: | DC24V/1.6A |
Customization: |
---|
Suppliers with verified business licenses
Constant temperature suspension type
|
16-XL
|
Executive standards
|
XF13-2006
|
Filling density
|
≤1000kg/M3
|
Fire extinguishing method
|
Fully flood extinguishing
|
Storage pressure
|
1.6MPa(+20°C)
|
Working temperature range
|
0~50°C
|
Max working pressure
|
2.5MPa(+50°C)
|
System spray time
|
Computer room≤8S,Others≤10S
|
Fire extinguishing design concentration
|
8-10%
|
Starting Method
|
Automatic, pneumatic, manual mechanical emergency start
|
Suppliers with verified business licenses